您现在的位置是:首页 > PLC技术 > PLC技术

STL编程语言中断电延时定时器

来源:艾特贸易2017-06-05

简介启动一个断电延时定时器完整的 STL 语句表如下: A Enable_input; FR Timer; A Start_input; L Duration; SF Timer; A Reset_input; R Timer; L Timer; T Binary_time_value; LD Timer; T BCD_time_value; A Timer; =T imer_status; 采用

    启动一个断电延时定时器完整的STL语句表如下:

   A    Enable_input;

   FR    Timer;

   A    Start_input;

   L    Duration;

   SF     Timer;

   A    Reset_input;

   R    Timer;

   L    Timer;

   T    Binary_time_value;

   LD    Timer;

   T    BCD_time_value;

   A    Timer;

   =T    imer_status;

    采用SCL,调用断电延时定时器编程如下:

   BCD_time_value:=S_OFFDT(

   T_NO=Timer,

   S  =  Start_input,

   TV  =Duration,

   R  = Reset_input,

   Q  = Timer_status,

   BI  :=Binary_time_value);